Description
The Wheelock POWERPATH (PS-8-LP) by Eaton is a supervised remote power supply/battery charger in a low profile cabinet that is used for supervision and expanded power driving capability of fire alarm Notification Appliance Circuits (NAC). The PS-8-LP is filtered and regulated and provides 8 amps of power distributed across 4 outputs.
The power supplies may be connected to any 12V or 24V (FWR or DC) Fire Alarm Control Panel (FACP) by using a NAC or a "Dry Contact." Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 24VDC, up to four (4) Class "B", two (2) Class "A", or two (2) Class "B" and one (1) Class "A" Notification Appliance Circuits. With the optional plug-in PS-EXP module the unit supports (8) Class "B" or (4) Class "A" Notification Appliance Circuits. Additionally, an auxiliary power output of 2.5 Amps (disconnected upon AC power loss or an alarm condition) or up to 0.240 A of constant power on the PS-8-LP.
The Wheelock power supplies can accommodate 7 AH batteries inside its lockable chassis. Using an external battery cabinet it can charge up to 33 AH batteries (pending UL testing). Two FACP NAC circuits or two "Dry" contact initiating circuits can be connected to the inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs. Each output is rated at 3.0 Amps (Class "B") or (Class "A") and can be programmed to generate a steady or Code 3 temporal horn sound and a strobe output under alarm condition. Total load for PS-8-LP NAC circuits must not exceed the power supplies rated output.
The power supplies under non-alarm condition provide independent supervision for Class "A" and Class "B" FACP NAC circuits. In the event of circuit trouble, the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are two sets of trouble reporting terminals, one used for AC power loss reporting and the other for all troubles. The AC power loss reporting, on the common trouble terminals and on IN1 or IN2, can be delayed for either 30 seconds or 170 minutes. The AC power loss terminals will always report the trouble within 1 second after loss of AC power.
The PS-8-LP power supplies are UL listed under UL Standard 864, 9th Edition to be used with any 24 volt listed regulated notification appliances. They include the capability to synchronize Wheelock strobes and horns and to silence the horn signal when horn/strobes are operating on two wires.
Features
- Low Profile
- Inputs
- 120VAC, 50/60Hz, 4.25 Amps and 5.32 Amps Operating Power in Alarm
- 240VAC, 60Hz, 3.22 Amps Operating Power in Alarm
- 24VDC Battery Backup Connection
- Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA)
- FWR or DC
- Two (2) "Dry" Contact initiating Circuits
- Accepts two (2) Class "A" or two (2) Class "B" circuit inputs
- Built in battery charger for sealed lead acid or gel type batteries
- Outputs
- NAC outputs are 24VDC, 3.0 Amps each, power limited
- 8 Amps on PS-8 -LP total alarm current
- Capable of four (4), Class "B" circuits
- Capable of two (2) Class "A" circuits
- Capable of one (1) Class "A" circuit and two (2) Class "B" circuits
- Capable of (8) Class “B” or four (4) Class “A” circuits with optional PS-EXP module
- Temporal (Code 3), constant voltage output, Wheelock Sync output or True input to output follower mode
- Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
- Input and output can be synchronized with “IN>OUT SYNC” mode (DSM, 2nd POWERPATH or FACP with synchronization protocol is required)
- Audible silence capability
- Filtered and electronically regulated output
- 2.5 Amp auxiliary power limited output with reset capability. (Removed upon AC loss or alarm. Automatic reset 30 seconds after AC power returns or the alarm condition is over) or 0.240 Amps PS-8-LP of auxiliary power limited output which remains on during AC loss or an alarm condition when configured for 24 hour battery backup
- Supervision
- Compatible with 12V or 24V (FWR or DC) FACP
- Signaling appliance circuits are supervised and steered to either IN1 or IN2
- 10K Ohm, 1 Watt (Wheelock Model #100651 PSEOL) End of Line Resistor (EOLR) for supervision of all outputs
- 37 distinguishable trouble diagnostics
- AC loss trouble reported over a separate set of contacts (delay of 1 second)
- All troubles are reported over the common trouble contacts (AC loss can have a delay of 30 seconds or 170 minutes)
- Automatic switchover to standby battery when AC fails
- Thermal and short circuit protection with auto reset
- Input and output status LED indicators
- AC fail supervision
- Battery presence and low battery supervision
- Ground Fault Detection, with diagnostics to indicate which circuit fault is on
- Latching LEDs for NAC trouble annunciation and Diagnostic trouble LEDs (latching can be disabled)
- Power
- Not battery dependent
- Automatic switch over to standby batteries when AC fails
- Supports sealed lead acid or gel type batteries
- Fused battery protection
- Thermal and short circuit protection with auto reset
- Supports 7AH batteries
- Compliance
- Approvals Include: UL Standard 864, UL 1481
- Compliant with NFPA 72
- Factory Mutual (FM)