Description
PFC-5008
Fire Alarm Control Panel
3992175
Potter's PFC-5008 Fire Alarm Control Panel is a microprocessor based unit designed for small to medium commercial, residential, multi-family, institutional and industrial occupancies. Fully configurable using DIP switches, it enables the user to configure the system to meet their specific requirements. The PFC-5008 is a PFC-5004E with the ZA42 expansion card factory installed. In addition, the preassembled kit contains a UDACT-9100 for digital communication.
The PFC-5008 comes standard with 8 Class B (Style B) Initiating Circuits which may be configured as 4 Class A (Style D) circuits. In addition, it comes equipped with 4 Class A/B (Style Z/Y) Indicating circuits which are each rated at 1.7 amps. The panel also includes a 5 Amp Power Supply which powers the system and supplies a 4-wire resettable regulated smoke power supply of 24 VDC 100mA maximum.
The PFC-5008 utilizes a simple DIP switch configuration for programming initiating and indicating circuits as well as the enabling and disabling of system functions such as Signal Silence, Fire Drill and Auxiliary Disconnect. Some predefined initiating circuits can optionally be configured Waterflow or Latching/Non-Latching Supervisory. In addition, the PFC-5008 allows for Alarm Verification on the initiating circuits. The indicating circuits may be configured as Silenceable or Non-Silenceable with the audibles configured for Steady, March-Time, Temporal Code, or California Code. Sync module required for strobe synchronization.
The PFC-5008 is equipped with auxiliary relay contacts for Common Alarm, Trouble and Supervisory. If no Supervisory circuits are enabled, the Supervisory relay becomes a second Alarm relay. The cabinet is available in a beige color for the Canadian market and a red exterior for the U.S. and International markets.
Features
- 8 Class B (Style B) 4 Class A (Style D) Initiating Circuits 4 Class A (Style D) circuits
- Predefined Initiating Circuits can be configured as Waterflow or Latching/Non-Latching Supervisory
- Selectable Alarm Verification on Initiating Circuits
- Zone Disconnect Switches
- 5 Amp Power Supply
- 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps max. per circuit)
- Audibles may be configured as Steady, Temporal Code, California Code, or March Time
- Auto Signal Silence
- Auxiliary relay contacts for Common Alarm, Common Trouble, and Common Supervisory
- Built-in RS-485 Interface for RA8F Multiplexed Remote Annunciators (Up to 3 Annunciators)
- Built-in Walk Test operation
- Output for 4-wire resettable regulated smoke power
- Easy configuration via DIP switches