Description
Altronix AL802ULADA NAC Power Supply, 2 Class A or 4 Class B Outputs, 24VDC @ 8A, 120VAC, Red BC400 Enclosure
Altronix AL802ULADA is an extremely cost effective voltage regulated remote NAC Power Extender. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC) expansion (supports ADA requirements) and providing auxiliary power to support system accessories.This product replaces AL800ULADA.
Features
- 2-wire horn/strobe Sync mode allows audible notification appliances (horns) and visual notification appliances (strobes) to be silenced/deactivated at the same time
- Sync protocols include Potter/Amseco, Gentex®, System Sensor®, and CooperWheelock®
- Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit)
- Compatible with 12VDC or 24VDC fire panels
- Output loop supervision steered to Input 1 or Input 2
- Signal circuit trouble memory (helps identify intermittent loop problems)
- Common trouble input and output for external trouble signals tie-in
- Ground fault detection
Specifications
- Input Voltage 120VAC, 60Hz, 4A
Two (2) Class A or two (2) Class B inputs
Two (2) NC dry contact trigger inputs - Input Ratings (INP1 and INP2) 8-30VDC 6.5mA max from FACP
12V 6.5mA, 24V 6.5mA from FACP - Output Voltage 24VDC power-limited outputs
- Output Current 8A max. total alarm current
2.5A max. current per output - Auxiliary 1 A
- Thermal and short circuit protection with auto reset
- Filtered and regulated outputs
- Programmable Supervised Indicating Circuit Outputs Four (4) Class B, or TWO (2) Class A, or One (1) Class A and Two (2) Class B
- Charging voltage 26.2-26.4VDC
- Built-in charger for sealed lead acid or gel type batteries
- Automatic switchover to stand-by battery when AC fails
- Zero voltage drop when switching over to battery backup
- AC Failure Form "C" contacts
- Battery Form "C" contacts (Batteries are sold separately)
- AC Power (Green LED) Input voltage is present
- DC Output (Red LED) Powered
- Logic Board (Red and Green LED) Output status
- Operating Temperature 0° C to 49° C (32° F to 120° F)
- Storage - 20° C to 70°C ( - 4° F to 158° F)
- Relative Humidity 85% +/- 5%
- BTU/Hr. (approx.) 31 BTU/Hr.
- Agency Listings Control Units and Accessories for Fire Alarm Systems (UL864)
CSFM - California State Fire Marshal Approved
MEA - NYC Department of Buildings Approved
NFPA 72 Compliant
FM Approved - Enclosure Specs Wall mount enclosure for indoor use
Dimensions 12.25"W x 15.5"H x 4.5"D (311 mm W x 394 mm H x 114 mm D)
1.125" and 1.375" combination knockouts - Product Weight 12 Lbs. (5.44 kg)
- Shipping Weight 13.3 Lbs. (6.03 kg)