Description
The CHG-120F is a state-of-the-art battery charging system designed for use with Fire-Lite fire alarm control panels (FACPs). It is designed to charge lead-acid batteries between 25 and 120 ampere-hours (AH).
Features
- Charges sealed lead-acid batteries
- Automatic float-type battery charger
- Rated for batteries of 25 to 120 ampere-hours
- Obtains full float voltage within 48 hours
- For use on any 24-volt FACP which can handle the specified batteries and can disable the local charger
- AC Fail delay (central station applications) per latest NFPA requirements
- Form-C Trouble contact
- Dual outputs, for easy load distribution
- Diagnostic LEDs:
- Primary AC On
- Charger Trouble
- Ground Fault
- Hi Charge
- Lo Charge
- Battery Voltage Level (3 LEDs)
- Low Battery
- Black or red BB-55F(R) battery cabinet
- Field-selectable input voltage, 120 VAC or 230 VAC
- Charges:
- 26 AH batteries within 9 hours
- 55/60 AH batteries within 20 hours
- 120 AH batteries within 38 hours
NOTE: Values per Fire-Lite testing.
Applications
Use the CHG-120F when batteries required for standby are rated between 25 to 120 AH.