StarLink MAX Fire SLE-MAXVI-CFB-PS 5G LTE-M Dual Path Cell. Comm. Fire Alarm Communicator Verizon Features
5G LTE-M Commercial Fire Alarm Communicator with Direct AC Power Supply (120VAC, 60Hz)
Supports both Sole Path (cellular only) and Dual Path (cellular + IP) communication for fire alarm reporting
Operates on the Verizon network and utilizes CAT-M1 technology for reliable cellular communication
Fully supervised, wireless, digital two-way subscriber unit
Compatible with 12V-24V fire alarm control panels (FACPs) using Contact ID and 4/2 protocols, including legacy panels
Replaces two traditional POTs lines per FACP, enabling significant cost savings over leased landlines
Equipped with four programmable EOLR (End-of-Line Resistor) zone inputs for flexible alarm integration
Includes two Form C relay outputs (dry contact, 30V AC/DC, 500mA max) for additional supervision or control—no extra supervision modules required
Provides two telephone-style jacks for easy FACP connection
Features patented Signal Boost™ circuitry and dual-diversity twin antennas for maximum signal acquisition and reliability, minimizing dropouts
Full data reporting to any central station nationwide, supporting both Verizon and AT&T networks (model dependent)
Monitored battery charging and active battery test circuits; requires a sealed lead acid battery (4AH to 7AH) for 24-hour standby (max charge current 200mA)
Trouble relay output (dry contacts) for dedicated "Communicator Trouble" zone; visual indicators for AC power, trouble, and battery status
Compliant with UL985, UL1023, UL1610, UL1076, UL864 10th Ed., California State Fire Marshal, and NYC FD requirements
Metal enclosure for commercial-grade installation; visible AC ON LED and trouble status LED on housing
Optional Wi-Fi connectivity via UL 864 Certified SLE-WIFI-MODULE for dual-path installations