Triple Status Control Module

Cornell Communications

SKU:
CNLNC102D

No Stock / Available to Order

Description

The NC-102D control module provides users with control over all functions associated with Cornell Multi-Status Emergency Call Systems. This control unit sorts calls from resident stations to the pre-set level of priority. This control module gives the user automatic control of both audible and visual notifications.

After a call has been placed, this module produces an audible tone at all duty stations, including the multi-status annunciator panel. The visual alerts are pre-set to three different levels, with each level indicating the priority of the patient call. The first priority is indicated by rapidly flashing lights and an audible beep every 1/2 second. Medium priority has a slower flashing light, with an audible beep every 1 second. The low priority calls get a steady-on indicator and one beep every 6 seconds. This control unit operates at 24VDC and is UL listed.

UL Listed CORNELL NC-102D Control Module provides reliable control over all functions of CORNELL'S Multi-Status Emergency Call Systems providing three levels of steady and flashing lights and tones to distinguish priorities within a nurse call system.

Operation:
Cornell's NC-102D directs the call from one of Cornell's stations to the predetermined level of priority.

Mounting:
Surface-mounted enclosure.

Engineering Specifications

The contractor shall furnish and install the CORNELL NC-102D Control Module. The NC-102D offers automatic control of both audible and visual notification. The audible tones shall be sounded at all duty stations and at the multi-status Annunciator panel whenever a call is placed. The NC-102D offers up to 3 levels of Priority, as follows:

  • First Level - Highest priority, rapid flashing indicator & one beep per 1/2 second
  • Second Level - Medium priority, slow flashing indicator & one beep per second
  • Third Level - Lowest priority, steady-on indicator & one beep every six seconds

Technical Information

  • Power Requirements: 24VDC
  • Operating Environment: 50-120°F Indoor Non-condensing
  • Physical Enclosure Dimensions: 7-1/4" W x 12" H x 3-1/2" D
  • Mounting: Surface mounted enclosure
  • Wiring: #22 AWG Minimum
  • Electrical Specifications: The NC-102D shall derive its operating voltage from the CORNELL P-512243A Power Supply. The NC-102D operates at 24VDC.
    P-, F- and S-, signal generators rated at 3A each. DN, DE & HI status outputs rated at .5A each