System Sensor's i3 Series photoelectric and photoelectric/ thermal smoke detectors represent a significant advancement in conventional detection, incorporating three key features: installation ease, intelligence, and instant inspection.
Installation ease. The i3 Series redefines installation ease with its plug-in design. This allows an installer to pre-wire the bases included with the heads. The large wire-entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of backbox mounting methods, as well as direct mounting with drywall anchors. To complete the installation, i³ Series heads plug into the base with a simple Stop-Drop 'N Lock™ action.
Intelligence. i3 Series detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms, to minimize nuisance alarms, are standard in the i3 Series.
Instant inspection. The i3 Series provides wide-angle red and green LED indicators for instant inspection of detector condition. The LEDs indicate: normal standby, out-of-sensitivity, alarm, or freeze trouble conditions. The "EZ Walk" loop test feature is available on two-wire i³ Series detectors when connected to the 2W-MOD loop test/maintenance module. The "EZ Walk" feature verifies the initiating loop wiring by providing LED status indication at each detector.
Features
- Plug-in detector line - mounting base included
- Large wire-entry port
- In-line terminals with SEMS screws
- Mounts to octagonal and single-gang backboxes, 4" (101.6mm) square backboxes, or directly to ceiling.
- Stop-Drop 'N Lock attachment to base
- Removable detector cover and chamber for easy cleaning
- Built-in remote maintenance signaling
- Drift compensation and smoothing algorithms
- Simplified sensitivity measurement
- Wide-angle, dual-color LED indication
- Loop testing via "EZ Walk" feature
- Built-in test switch
Specifications
- Operating Temperature Range: 32°F to 120°F (0°C to 49°C)
- Sensitivity: 2.5% foot (0.762% meter) nominal
- Input Terminals: Utilize 14 to 22 AWG wire
- Dimensions (including base): 5.3" (134.62 mm) diameter, 2.0" inches (50.8 mm) high
- Weight: 6.3 oz. (178.6 grams)
- Mounting Options: 3.5" (88.9 mm) octagonal backbox; 4" (101.6 mm) octagonal backbox; single-gang backbox; 4" (101.6 mm) square backbox with a plaster ring; or direct mount to ceiling
- Operating Voltage: 12/24 V non-polarized nominal; 8.5 V minimum; 35 V maximum
- Maximum Alarm Current: 130 mA limited by control panel